Section 15.4.14 · Chapter 15: Using Macros
System Service
■ GET_RTC
| Format | GET_RTC(P1 ) | Data Type | U | |||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Function | Gets the data of the real time clock and saves the result in P1. | |||||||||||||||||||||||||||||
| P1 (I) |
The starting location of the memory block that is used
as an RTC data block to receive the operation result.
The structure of the RTC data block is shown below:
An RTC data block requires 8 words. |
|||||||||||||||||||||||||||||
| Example 1 | GET_RTC($U100) /* Get the data of the real time clock. The second will be in $U100 and the day-of-week will be in $U107. */ | |||||||||||||||||||||||||||||
■ SET_RTC
| Format | SET_RTC(P1 ) | Data Type | U |
|---|---|---|---|
| Function | Sets the real time clock using the data in P1. | ||
| P1 (I) | The starting location of the memory block that is used as an RTC data block to contain the new settings for the real time clock. See the description of GET_RTC to know the structure of the RTC data block. | ||
| Example 1 |
$U100 =
0 // Second $U101 = 30 // Minute $U102 = 8 // Hour $U103 = 0 // Adjustment $U104 = 1 // Day $U105 = 7 // July $U106 = 10 // Year 2010 $U107 = 4 // Thursday SET_RTC($U100) /* Set the real time clock to 8:30:00 July 1st 2010 Thursday */ |
||
■ SYS
| Format | SYS(P1,P2,P3) | Data Type | U |
|---|---|---|---|
| Function | Requests system service P1 with the arguments P2 and P3. This command is reserved for system use. | ||
| P1 (I) | The code of the system service. | ||
| P2,P3 (I/C) | The arguments of the system service. | ||
| Example 1 | SYS(0x6630, 0, 0) /* Restart the application */ | ||
| Example 2 | SYS(0x6631, 0, 0) /* Run Panel Setup */ | ||
| Example 3 | Generate a random number. The random number generation starts from a seed value, so you must do initialization first. | ||
|
SYS(0x63A1,0,0)
/* Initialize a seed value for a
random number. */ SYS(0x63A2,0,0) /* Generate a random number and save it into $S521*/ W220 = $S521%255 + 1(S) // Get a random number between 1 and 256 |
|||
| Example 4 | Calculate the relative humidity with given temperatures of dry bulb and dew point, please see 15.4.14.1 Calculating Relative Humidity.htm for details | ||
|
$U200 =
70 (F)
// Set the dry bulb temperature in
Celsius
$U202 = 65 (F) // Set the dew point temperature in Celsius SYS(31,1,$U200) // Calculate the relative humidity // The result is saved in $U204 and $U205 and should be 80.2547 |
|||
■ SetBacklight
| Format | SetBacklight(P1) | Data Type | U | ||||||
|---|---|---|---|---|---|---|---|---|---|
| Function | Switches the LCD backlight. | ||||||||
| P1 (I/C) |
Specifies the switch operation.
|
||||||||
| Example | SetBacklight(0) /* Turn off the backlight. */ | ||||||||
■ SetScreenSaver
| Format | SetScreenSaver(P1) | Data Type | U |
|---|---|---|---|
| Function | Sets the wait time of the screen saver. | ||
| P1 (I/C) | The wait time. The time unit is minute. The screen saver is disabled when the wait time is 0 | ||
| Example | SetScreenSaver(20) /* Set the wait time of the screen saver to 20 minutes. */ | ||
■ SetIdleProc
| Format | SetIdleProc(P1,P2) | Data Type | U | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Function | Sets the properties of the idle processing. | ||||||||||||
| P1 (I/C) |
Specifies the setting operation
|
||||||||||||
| P2 (I/C) |
Specifies the property of the designated operation.
|
||||||||||||
| Example | SetIdleProc(2, 10) /* Set the idle screen to screen No. 10. */ | ||||||||||||
■ GetID
| Format | P1 = GetID(P2) | Data Type | U | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Function | Gets P2 type of the identifier of the HMI unit and saves the result starting from P1. | ||||||||||||||
| P1 (I) |
The starting location of the memory block to save the
identifier. Two kinds of data can be used as the identifier of an HMI unit, which are the product serial number and the MAC address of an Ethernet port. The required sizes of memory to save the two kinds of identifiers are different. The product serial number needs seven words because the serial number is a string with 14 characters. The MAC address needs six words because the address is composed of 6 numbers. |
||||||||||||||
| P2 (I/C) |
The type of the identifier. The following table describes the type codes and the supporting HMI models:
|
||||||||||||||
| Example |
$U100 = GetID(0)
/* Get the HMI’s serial number. The
result is saved in $U100-$U106 */ $U110 = “07WT4DX1130118” $U120 = STRNCMP($U100, $U110, 14) /* Set $U120 to 0 if the identifier is 07WT4DX1130118 */ |
||||||||||||||
■ SetBrightness
| Format | SetBrightness(P1 ) | Data Type | U |
|---|---|---|---|
| Function | Sets the brightness of the LCD. | ||
| P1 (I/C) | Specifies the brightness level. A valid level is between 0 and 15. Level 0 is the darkest and level 15 is the brightest. | ||
■ SetBriRange
| Format | SetBriRange(P1,P2) | Data Type | U |
|---|---|---|---|
| Function | Sets the adjustable range of the LCD brightness. The range is determined by two values: the darkest percentage and the brightest percentage. | ||
| P1 (I/C) | Specifies the darkest percentage which is the percentage of the least brightness that is allowed to set to the full brightness of the display. A valid value is between 0 and 99 and must be less than the brightest percentage. | ||
| P2 (I/C) | Specifies the brightest percentage which is the percentage of the most brightness that is allowed to set to the full brightness of the display. A valid value is between 1 and 100 and must be greater than the darkest percentage. | ||
| Example | SetBriRange(10, 85) /* The adjustable range is between 10% and 85% of the full brightness when the darkest percentage and the brightest percentage are 10 and 85 respectively. */ | ||
In this section
Need PM Designer itself?
V4 for current PK, PT, ITV and PM panels, V2 for older models. Free, sent by email.
Source.Section 15.4.14 of the PM Designer Software User Manual, Edition 2.0, © Cermate Technologies Inc. (www.cermate.com, service@cermate.com). Reproduced online, with the manual's own figures, by TSL Automation Solutions, authorised Cermate distributor, for users of Cermate HMI panels. PM Designer and PanelMaster are trademarks of Cermate Technologies Inc.