Panel-Mount HMI and Panel PC Installation: Cut-outs, Gaskets and IP65

TSL Automation Solutions November 18, 2026
Rear view of a 7-inch Cermate HMI fitted in a control panel door cut-out with mounting clips
Share

Table of Contents

To keep IP65 at the front of a panel-mounted HMI or panel PC, cut the opening to the cut-out size in the product's own drawing, mount it in a panel that is flat and stiff enough not to bow, tighten the clips or brackets evenly to the maker's torque (until the bezel just meets the panel, no further), and keep the gasket clean, seated and undamaged. The IP65 on the datasheet describes the sealed front face, tested to IEC 60529, and it only holds when the unit is installed the way the manufacturer intended.

This guide goes through each step with real figures from the Cermate HMIs and Avalue panel PCs we supply: cut-out sizes, panel thickness, mounting torque, what the rating does and does not cover, heat, and cable strain relief.

What the IP65 on the datasheet actually covers

IP codes are defined in IEC 60529 (published in Europe as EN 60529). The first digit is protection against solids and the second against water (Tameson IP rating chart):

  • First digit 6: dust tight, full protection against dust.
  • Second digit 5: low-pressure water jets from any angle. The test lab DLS describes the IPX5 test as water from a 6.3 mm nozzle at 12.5 litres per minute, from 2.5 to 3 m, for at least three minutes (DLS: IPX5 and IPX6 testing).
  • Second digit 6: powerful jets, about 100 litres per minute from a 12.5 mm nozzle, with the same timing (DLS).

Two points matter for installation. First, a panel-mount unit is usually rated at the front only, because the rear sits inside a cabinet. Avalue says so explicitly: the ARC-15W42 record lists "Front panel IP65" and "Back cover IP41 (except I/O)", and the ARC-1538 lists front IP65 and rear IP41. A rear of IP41 is not meant to be hosed. Second, the front rating is only as good as the joint between bezel, gasket and panel, which is the part you build. Cermate makes this explicit on its IPM2 series: the IP65 on the IPM210 is stated with the condition "use screw-free lock, the thickness of the plate needs to be ≧ 2~3mm".

Model (from our records)Rating as listedWhat it tells the installer
IPM210 (10.1-inch HMI)IP65, using the screw-free lock in a plate of at least 2 to 3 mmFront seal depends on the supplied lock and a stiff enough panel
IPK2070-31ST (7-inch HMI)IP65Front-face rating for a cabinet door or console
IPT2070-51ST (7-inch HMI)NEMA Type 4X / IP66Higher water rating; the PT2 installation guide adds "NEMA Type 4X Indoor Use Only"
ARC-15W42 (15.6-inch panel PC)Front panel IP65, back cover IP41 (except I/O)Seal the front; keep the rear dry inside the enclosure
SPC-1533-B1 (15-inch stainless panel PC)Whole system IP69K, IP66A whole-unit rating, for washdown; see our IP69K washdown guide

If the cabinet itself is not sealed to the same level, the HMI front rating does not make the cabinet waterproof. Our IP rating guide covers the codes in more depth.

Cut-out dimensions: take them from the model, not the screen size

Screen size is not a cut-out size. Three 7-inch Cermate HMIs need three different openings, and two 10.1-inch models differ by 7 mm in width and 31 mm in height. These figures are from our product records (Cermate's "Cutout Dimension A x B"):

ModelScreenCut-out (mm)Outer size W x H x D (mm)
IPM2077 inch185 x 128197 x 140.1 x 25.7
IPT2070-WST4B7 inch175 x 132.5 (noted as compatible with the PT070 cut-out)189.6 x 144.9 x 36.1
IPK2070-31ST / IPT2070-51ST7 inch191.5 x 138203.5 x 148.8 x 31.6 / 203.5 x 148.5 x 37.1
IPM21010.1 inch252 x 170267.1 x 185.1 x 26.1
IPK2100-31ST / IPT2100-51ST10.1 inch259 x 201270.1 x 212.1 x 37.98 / 43.48
IPK2120-31ST / IPT2120-51ST12.1 inch302 x 228335.4 x 245.9 x 60.9 / 335.4 x 245.8 x 66.4
IPK2150-31ST / IPT2150-51ST15 inch384.5 x 283399.1 x 297.6 x 57.9 / 63.4

Three practical consequences:

  • Retrofits. Replacing an old HMI is easiest when the new one fits the existing hole. The IPT2070-WST4B exists for exactly that reason: its record notes a cut-out compatible with the PT070. Within the current range, the IPK2 and IPT2 models of the same size share a cut-out, so you can move between them without touching the door.
  • Tolerance. Cermate's PT2 installation guide gives a single nominal L x H for each model and no tolerance (Cermate PT2 series installation guide V2.5). Treat it as the target, not a minimum: an oversize hole leaves the gasket bridging air at the edges. Cut, deburr, check the corners are square and offer the unit up before painting or final assembly.
  • Depth. Check the depth behind the door including connectors. Several Cermate records state whether the depth includes the 5-pin terminal block; add the bend radius of the cables on top.

For Avalue panel PCs, our records give the outer dimensions and "Panel mount with mounting kits" (the ARC-15W42 is 391.21 x 293.21 x 61 mm, the ARC-1538 350.51 x 274.51 x 54.5 mm) but not a cut-out figure. Do not derive the opening from the outer size: ask us for the mechanical drawing of the exact model and mounting kit before the panel is cut.

Panel thickness and stiffness

The gasket can only seal against a surface that stays flat. A thin door that bows when the clips are tightened opens a gap along the long edges, often in the middle of the span where you cannot see it. The only panel thickness figure in our Cermate records is the IPM2 condition of a plate at least 2 to 3 mm thick for IP65. For other models, ask for the panel thickness range from the installation drawing and check two things on site:

  • Large openings in thin sheet steel weaken the door. A 15-inch cut-out takes out most of a small door; stiffen the area around it if the door flexes by hand.
  • Painted or powder-coated panels can have runs and drips at the edge of the cut-out. The gasket must sit on a flat, clean face, so keep the sealing area free of coating build-up and burrs.

Mounting clips, brackets and torque

Cermate's PT2 installation guide (which covers the IPT2 models such as the IPT2070-51ST and IPT2100-51ST) shows two ways to fix the unit: plastic locks and metal locks with a fixing screw. For the screws it gives a suggested torque of 0.25 to 0.34 Nm and the instruction to tighten each fixing screw until the bezel corner gets in contact with the panel; the Chinese text of the same note warns against over-tightening (Cermate PT2 guide).

That is a small torque, so a cordless driver is the wrong tool here. Over-tightening crushes the gasket at the clip points and leaves it under-compressed between them, bows a thin door, and can crack a plastic bezel. A sensible sequence is:

  1. Fit all clips loosely, evenly spaced around the bezel.
  2. Bring each one to light contact, working across opposite sides rather than round in order.
  3. Finish to the specified torque in a second pass, checking that the bezel sits evenly against the panel all round.

For Avalue panel PCs, panel mounting uses the model's mounting kit; use the brackets and screws supplied for that model and the torque in its manual rather than a figure from another product.

Gasket care

The gasket is the seal, and the HMI cannot compensate for one that is dirty, twisted or tired:

  • Check it is fully seated in its groove and not twisted, stretched or pinched at a corner before the unit goes into the hole.
  • Keep the gasket and the panel face clean. Swarf, paint flakes or a cable tie offcut under the gasket is a leak path.
  • Do not add silicone between gasket and panel unless the manufacturer approves it; it can stop the gasket seating evenly.
  • When a unit is removed after years in service, inspect the gasket. If it is flattened, cracked or hardened, fit a new one for that model rather than reinstalling the old one.
  • Check the clips after the first weeks of vibration or heavy door use.

Heat and ventilation clearances

A panel-mount unit sheds its heat into the cabinet, and what counts is the air temperature inside the enclosure, not the room. The records give operating ranges of -10 to 60°C for the Cermate IPK2 and IPT2 HMIs and -10 to 50°C for the ARC-15W42 and ARC-1538 panel PCs. Cermate's PT2 guide adds that for UL 61010-2-201 the unit shall be mounted in an industrial control panel whose ambient does not exceed 60°C, and lists the maximum rated ambient as 60°C for the PT2043 to PT2104 and 70°C for the PT2120, PT2121 and PT2150 (Cermate PT2 guide).

The Avalue models above are fanless, so they rely on air moving over their rear housing. Keep the clearance behind and around the unit that the manufacturer's drawing shows, do not bury it against drives or power supplies, and add cabinet cooling if the enclosure runs hot. Our article on thermal management in fanless industrial PCs explains why.

Cable strain relief and wiring

A door-mounted HMI moves every time the door opens, so its cables flex at the connectors. The PT2 guide suggests AWG 18 to 24 wire with matching pin terminals for the terminals, a terminal screw torque of 4.60 lb-in with a warning against excessive force, input wiring rated at least 90°C, and a SELV or double-insulated power supply (Cermate PT2 guide). On top of that:

  • Clamp the power, serial and Ethernet cables to the door or a bracket close to the unit, so their weight does not hang on DB9 or RJ45 connectors.
  • Leave a service loop across the hinge, so opening the door bends the loop and not the connector.
  • Connect the FG (frame ground) terminal on the power connector, and route serial and Ethernet cables away from motor and drive cables.
  • Remember the rear of a front-rated unit is not sealed: keep cable entries into the cabinet sealed to the cabinet's own rating.

Installation checklist

  1. Cut-out taken from the exact model's drawing or record, cut to nominal, deburred and square.
  2. Panel flat, stiff and within the maker's thickness range (IPM2: at least 2 to 3 mm).
  3. Gasket clean, seated and undamaged; sealing face free of paint runs.
  4. Clips tightened evenly, across opposite sides, to the stated torque (PT2: 0.25 to 0.34 Nm), bezel in even contact.
  5. Cabinet temperature within the unit's rating, with clearance behind fanless units.
  6. Cables clamped, service loop across the hinge, FG connected.
  7. Whole-unit washdown? Then a front-sealed unit is the wrong choice; specify a whole-system rated panel PC.

If you are still choosing the unit, our HMI buying guide and the compare tool help narrow it down.

How TSL can help

TSL Automation Solutions, based in Mumbai, has been an authorised Cermate and Avalue distributor since 2015 and ships worldwide. We supply Cermate HMIs in 4.3 to 15-inch sizes, including the IPM210, the IPK2 series such as the IPK2070-31ST, and IPT2 models rated NEMA Type 4X / IP66 such as the IPT2100-51ST, as well as Avalue industrial panel PCs like the ARC-15W42 and stainless steel panel PCs for washdown areas. Ask us for the cut-out drawing, mounting kit and installation guide of the exact model before you cut the panel; the product finder helps you shortlist by size and rating.

Send us the model numbers and quantities and we will reply with availability and lead time within one business day.

Frequently Asked Questions

Tags: panel mount hmi cutout ip65 panel mount installation hmi cutout dimensions hmi mounting clips torque hmi gasket panel pc panel mount front ip65 rating
Found this useful? Share it
T

TSL Automation Solutions

Head of Marketing, TSL Automation Solutions

Sanjana covers industrial automation trends, product launches, and technology insights for TSL Automation Solutions, a Mumbai-based distributor of HMI, Panel PC, and embedded computing systems serving manufacturers across India and globally.

Need help choosing the right product?

Our team in Mumbai can recommend the right HMI, Panel PC, or embedded system for your application.

Contact TSL Automation