The following operation options can be added to a numeric entry. Select and set
up the options in the Numeric Entry property sheet.
|
Operation
|
Description |
|
Scaling |
Gain/Offset |
The value of the monitored variable will be displayed in
a scaled manner. The following is the scaling formula.
DisplayedValue = MonitoredValue * Gain + Offset
If the option is selected, the entered value will be
scaled by the following formula with the same
coefficients (Gain and Offset) before it is output.
OutputValue = (EnteredValue – Offset) / Gain
Select and set this option in the Advanced page.
Note: The Gain and Offset are 32-bit
floating point numbers. They have, at most, 6
significant digits. Rounding and truncation errors may
occur. |
|
Max./Min. |
Set the Display Min/Max corresponding to the Data
Min/Max. If this option is selected, the value of the
monitored variable will be scaled to fit the display
range before displayed. And the entered value will be
scaled to fit the data range before it is output. |
|
Range Check |
Numeric entry will verify an entered value according to
the specified maximum and minimum. If the entered value
is not within the allowable range, the value will not be
output. Select and set this option in the Advanced page.
Note 1: When the scaling option is
selected, the output value is verified instead of the
entered value.
OutputValue = (EnteredValue – Offset) / Gain
Note 2: When the scaling option is
selected, the allowable maximum and minimum shown on the
numeric keypad are the scaled versions of the specified
maximum and minimum.
ScaledMaximum = Maximum * Gain + Offset
ScaledMinimum = Minimum * Gain + Offset |
|
Touch Operation Control |
You can enable or disable the touch operation of the
object by the specified bit or by the current user
level. Select and set up this option in the Advanced
page. |
|
Timeout |
If the keypad for data entry receives no input for the
specified time period, the data entry operation will be
cancelled. |
|
Notification |
The Object will notify the specified bit of a successful
data entry operation. Select and set up this option in
the Advanced page. |
|
Operator Confirmation |
When a value is entered by the operator, the
Confirmation box will be displayed to receive the
operator’s confirmation. If the operator selects “Yes”,
the object will write the entered data to the specified
variable. If the operator selects “No” or the operator
does not respond within the specified time period
(Maximum Waiting Time), the data entry operation will be
cancelled.
Select and set up this option in the Advanced page. |
|
Change User Level |
The current user level can be changed after the
operation is performed. Select and set up this option in
the Advanced page. |
|
Operation Logging |
The entered value and the time of the data entry will be
recorded. Select and set up this option in the Advanced
page. |
|
Present the keypad at random position to lengthen the
life of touch panel |
The keypad is shown at the random position to lengthen
the life time of touch panel. Select and set up this
option in the Advanced page. |
|
Designated Keypad |
The Object will have its own keypad other than the
system keypad or the customized keypad for the whole
panel. Select and set up this option in the Advanced
page. |
|
Visibility Control |
You can show or hide the object by the specified bit or
by the current user level. Select and set up this option
in the Visibility page. |
|
Macro |
Numeric entry can run a macro before or after setting a
value to the specified variable. Specify and edit the
macro in the Macro page. |
Source.Section 7.1.1 of the PM Designer Software User Manual, Edition 2.0, © Cermate Technologies Inc. (www.cermate.com, service@cermate.com). Reproduced online, with the manual's own figures, by TSL Automation Solutions, authorised Cermate distributor, for users of Cermate HMI panels. PM Designer and PanelMaster are trademarks of Cermate Technologies Inc.