This section describes how to define the general settings for the picture
displays. The following is an example of the General page of the Picture Display
property sheet.

The following table describes each property in the General page.
|
Property
|
Description |
|
ID |
The object’s identifier. It is
generated when the object is
created. The identifier is
unique within the screen where
the object is located. The
format of the IDs for the
picture displays is PDnnnn. |
|
Note |
You can type a note for the
object. |
|
Shape |
Shape |
Check this option if you want
the picture display to have a
frame. |
|
Shape settings |
For details about the following
properties, see
Section
4.3.4 Setting up the Shape of an
Object.
,
Border Color, Pattern, FG Color,
BG Color |
|
External Label |
Check this option if you want
the picture display to have an
external label. Set up the
external label in the External
Label page. |
|
State |
Select a state as the current
state of the picture display so
you can view and set the
Pattern, FG Color, BG Color for
that state. |
|
State Type |
Bit |
The state type of the variable
that controls the picture
display. For details, see
Section
9.5.1 Basic Operations. |
|
Value |
|
LSB |
|
Animation |
|
Display a picture loaded by an associated function
button |
You can display a JPEG picture
at runtime loaded by the
function "Load JPEG Picture" of
a function button. This option
is only available for X-series
HMI units.
For details, please see
Section 5.4.1 Basic Operations
of function buttons. |
|
Data Type |
The data type of the variable
that controls the picture
display. The supported data
types include: Bit, 16-bit
Unsigned Integer, 16-bit BCD,
32-bit Unsigned Integer, and
32-bit BCD. |
|
Monitor Address |
Specifies the variable that
controls the picture display.
Click
to enter an address for this
field. Click
to select a tag for this field. |
|
Total State |
The number of states for the
picture display. |
|
Animation Frequency (Hz) |
The rate to change the picture.
|
Source.Section 9.5.4 of the PM Designer Software User Manual, Edition 2.0, © Cermate Technologies Inc. (www.cermate.com, service@cermate.com). Reproduced online, with the manual's own figures, by TSL Automation Solutions, authorised Cermate distributor, for users of Cermate HMI panels. PM Designer and PanelMaster are trademarks of Cermate Technologies Inc.
Text and figures are the manufacturer's and may describe features your panel or software version does not have. For a plain-language introduction read the PM Designer guide; for help with a specific panel contact TSL Automation.